MODULE 03 · BASICS

Basic components every HVAC technician should know

Identification, function and checks: capacitors, contactors, compressors, sensors, transformers, fuses, solenoid valves and dampers.

Beginner10 leccionesEdition: Oct. 20, 2026

LESSON 03.1

Single and dual capacitors: identify before connecting

Capacitance is expressed in farads; these components usually use µF, microfarads. Hz indicates frequency. The nameplate AC voltage is another component characteristic. Start and run capacitors have different functions and operating conditions.

In a dual capacitor, C is common to its two sections, HERM identifies the compressor section and FAN the fan section. Read the markings and trace each conductor on the model diagram; do not infer connections from color, tab count or position. Capacitor C does not automatically connect to compressor C.

Study capacitance measurement with the component isolated, de-energized and stored energy controlled according to the procedure. Check C–HERM and C–FAN separately against rating, tolerance and instrument accuracy. Short-circuit discharge is not taught.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Dual capacitor: C, HERM and FAN

TEMCo RC0102: 35/5 µF, ±5%. Two sections share C. Select a section to measure µF in this isolated, discharged virtual model. Hz is frequency, not capacitance.

Circuit symbols
Dual capacitor: C, HERM and FANTEMCo RC0102: 35/5 µF, ±5%. Two sections share C. Select a section to measure µF in this isolated, discharged virtual model. Hz is frequency, not capacitance. C · capacitor common → HERM · compressor section → FAN · fan sectionDE-ENERGIZED · ISOLATED COMPONENTCHERMFAN35 µF5 µFC–HERM: 35.0 µFCapacitor C ≠ compressor CµF

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

C–HERM · 35 µF ±5% · Section interval: 33.25–36.75 µF. Hypothetical reading: 35.00 µF. Reading within nominal tolerance. Also consider accuracy and procedure; this does not certify the capacitor.

Think before continuing

Does a 35 + 5 µF label mean measuring 40 µF between C and HERM?

Show explanation

No: there are two sections. In this example, C–HERM corresponds to 35 µF and C–FAN to 5 µF. Evaluate them separately using the nameplate tolerance.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

What information is missing if someone asks for “a capacitor the same size”?

View the explained answer

Function, µF for each section, tolerance, allowed voltage and frequency, terminals and equipment approval; physical size is not enough.

LESSON 03.2

Magnetic contactors: ratings, contacts and coil

A contactor separates control from load. In the referenced families, L identifies line, T load and A1/A2 the coil. Pole counts and auxiliary contacts vary. FLA, LRA and resistive-load ratings are different specifications; select for the application and exact coil, including AC/DC and frequency.

To study continuity of contacts normally operating at line voltage, the example is first fully de-energized and isolated. Check each pole in its defined states. An NO contact that stays closed at rest needs investigation; a beep alone does not evaluate loaded voltage drop or insulation.

Check coil resistance in Ω using its part number and procedure. OL can indicate an open circuit; a finite reading does not rule out shorted turns or actuation problems. There is no universal resistance range, and AC coil current is not calculated from V/R alone.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Contactor: poles and coil

Ideal two-pole NO contactor. The drawing changes position without energizing real equipment. L/T identify power terminals; A1/A2 identify the coil.

Circuit symbols
Contactor: poles and coilIdeal two-pole NO contactor. The drawing changes position without energizing real equipment. L/T identify power terminals; A1/A2 identify the coil. Pole L1–T1 → Pole L2–T2 → Coil A1–A2DE-ENERGIZED · ISOLATED COMPONENTL1L2T1T2A1A2K1Example NO polesL1–T1: Open · L2–T2: Open

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

L1–T1: Open · L2–T2: Open. DE-ENERGIZED · ISOLATED COMPONENT

Think before continuing

Is a higher-amp contactor always a suitable replacement?

Show explanation

No. Check poles, load application, FLA/LRA, voltage, AC/DC coil and frequency, auxiliary contacts and equipment approval.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

What does continuity between L1 and T1 prove with a closed pole?

View the explained answer

That an electrical path exists under those test conditions. It does not certify the complete contactor or its operating capability.

LESSON 03.3

Compressors: function and motor families

The compressor raises vapor pressure in the refrigerant circuit. Diagnosis combines electrical, refrigeration, control and mechanical evidence. One winding-resistance or current reading cannot establish the entire compressor’s condition.

In the displayed single-phase model, C is common, R run and S start: C–R and C–S are the two windings; R–S traverses them in series. Check actual values and terminal positions in the manual. An open thermal protector can affect readings. Insulation tests require the manufacturer’s method.

A three-phase or inverter-driven compressor needs its own identification and procedure; do not impose the C/R/S drawing on it. Do not apply an insulation test through connected electronics.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Single-phase compressor: C, R and S

Teaching equivalent of two single-phase windings, without a supply. It does not apply directly to three-phase or inverter compressors.

Circuit symbols
Single-phase compressor: C, R and STeaching equivalent of two single-phase windings, without a supply. It does not apply directly to three-phase or inverter compressors. C · motor common → C–R · run winding → C–S · start windingDE-ENERGIZED · ISOLATED COMPONENTCRS1 Ω2 ΩC–R = 1 Ω

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

C–R = 1 Ω. Hypothetical winding values; not a compressor specification.

Think before continuing

If C–R = 1 Ω and C–S = 2 Ω in this example, what do you expect between R and S?

Show explanation

Approximately 3 Ω, accounting for lead and connection effects. This sum does not prove correct insulation or compressor mechanical health.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Does the correct resistance sum rule out a mechanical fault?

View the explained answer

No. It only checks a circuit relationship under the measurement conditions; the other specified checks are still needed.

LECCIÓN 03.4

Temperature sensors: type, curve and context

NTC resistance falls as temperature rises; PTC resistance rises within its operating range. The graphic uses typical points from two identified CAREL references with their units. It does not treat every sensor as “10 kΩ”.

Interpret readings using actual temperature, isolated sensor resistance, the correct table and tolerance. Also check the signal or input expected by the controller. RTDs, thermocouples and active sensors use other principles; continuity does not prove accurate measurement.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Temperature and resistance: NTC / PTC

Three typical CAREL points: NTC 10 kΩ / β3435 and PTC KTY81/121. These are not a universal table or acceptance limits.

Circuit symbols
Temperature and resistance: NTC / PTCThree typical CAREL points: NTC 10 kΩ / β3435 and PTC KTY81/121. These are not a universal table or acceptance limits. Sensing element → Resistance and temperature → Control inputCAREL · NTC 10 kΩ / β3435NTC10000 Ω25 °CReferenceResistive sensor

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

NTC 10 kΩ / β3435 · 25 °C → 10000 Ω. Typical CAREL reference value; check the installed sensor table and tolerance.

Think before continuing

Do all “10 kΩ” sensors have the same curve?

Show explanation

No. That rating needs a reference temperature; curve, tolerance and controller compatibility also matter.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

A sensor reads 10 kΩ. Do we now know its temperature?

View the explained answer

Only if its type, curve and conditions are known. For the example NTC it is the typical value at 25 °C; it is not a rule for every sensor.

LECCIÓN 03.5

Normally open and normally closed

NO and NC describe contacts relative to a reference condition. For a relay it is usually the de-energized coil; for pressure controls, check how the manufacturer represents pressure and actuation. Actual state may differ from the drawn normal state.

A permission circuit may include several contacts: if one opens, that path is interrupted. Before attributing a fault, identify its actuating variable and whether opening is a valid protective response. Never bypass safety to turn a study result into an operating command.

THEORY → DIAGRAM → VIRTUAL PRACTICE

NO and NC: the reference state

NO = normally open; NC = normally closed, relative to a defined reference state. They do not mean “equipment running” or “equipment faulty”.

Circuit symbols
NO and NC: the reference stateNO = normally open; NC = normally closed, relative to a defined reference state. They do not mean “equipment running” or “equipment faulty”. NO contact → NC contact → Device referenceNOOpenNCClosedTwo independent contacts; defined reference state

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

NO: Open · NC: Closed.

Think before continuing

Does an NC contact always have continuity?

Show explanation

No. It describes its normal reference state; it may open when actuated.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Does “normally closed” mean “never opens”?

View the explained answer

No. It can open when actuated. Interpret the reference state and device sequence.

LECCIÓN 03.6

High and low pressure: switch or transducer

A pressure switch changes contacts at defined conditions. High and low pressure do not share universal settings: cutoff, differential and reset depend on product code and application. A protective shutdown does not prove a faulty pressure switch.

A transducer provides a pressure-related signal. The AKS 32R example is ratiometric: with a nominal 5 V DC supply it provides 0.5–4.5 V DC between its range endpoints. Signal-to-pressure conversion requires the exact range; do not test it as a contact or apply 24 V by analogy with other controls.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Pressure switch and transducer: two signals

Choose contact-based permission or an analog signal. Physical pressure and electricity are different domains.

Functional diagram
Pressure switch and transducer: two signalsChoose contact-based permission or an analog signal. Physical pressure and electricity are different domains. High pressure → Low pressure → Controller signalPermissionControlHighLowClosedClosedPermission path closed in this example.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Permission path closed in this example.

Think before continuing

Is an active transducer diagnosed like a switch?

Show explanation

No. Identify its supply, output, range and exact procedure. Do not bypass safeties to force equipment operation.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Does an open protective device justify bypassing it?

View the explained answer

No. First identify the condition that caused opening and follow the equipment procedure.

LECCIÓN 03.7

24 V control transformers

A transformer has primary and secondary windings; in this example they are separate circuits and energy transfer is magnetic. Nominal output is 24 V AC. The nameplate defines voltages, frequency and VA rating; do not change taps or assume compatibility from appearance.

The TR40VA002US datasheet specifies 40 VA with a 24 V AC secondary. The nominal quotient is approximately 1.67 A. Actual selection considers simultaneous loads, inrush, temperature and specified protection. Winding continuity does not prove correct turns ratio or insulation.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Transformer: 24 V AC and VA rating

TR40VA002US nominal example: 120 V AC primary, 24 V AC secondary, 40 VA. The exercise adds loads; it does not size protective devices.

Circuit symbols
Transformer: 24 V AC and VA ratingTR40VA002US nominal example: 120 V AC primary, 24 V AC secondary, 40 VA. The exercise adds loads; it does not size protective devices. Primary → 24 V AC secondary → Control loadTR40VA002US · 40 VA120 V CA/AC24 V CA/AC24 VAPrimarySecondaryWinding symbol; does not indicate the number of turns.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Hypothetical load: 24 VA / 24 V = 1.00 A. Nominal rating: 40 VA / 24 V ≈ 1.67 A. Within the nominal 40 VA; inrush and conditions still need checking. This calculation does not select the fuse.

Think before continuing

Is a 48 VA load within a 40 VA nominal rating?

Show explanation

No. It exceeds the example rating. Even below 40 VA, inrush, conditions and approved selection need checking.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Does 40 VA / 24 V automatically determine the fuse to install?

View the explained answer

No. It is a nominal relationship; protection comes from the applicable specification.

LECCIÓN 03.8

Fuses: recognize an opening and its cause

A fuse interrupts the circuit under the conditions of its time-current characteristic. Study resistance checks with it isolated and de-energized. An open-circuit reading alone does not explain why it opened.

Replacement requires suitable current, applicable AC/DC voltage, class, interrupting rating and timing behavior. Interrupting rating is not operating amperage. Investigate overcurrent or faults according to the procedure; never bypass or oversize to prevent opening.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Fuse: continuity and selection

Isolated, de-energized component. Recognizing an open circuit is different from choosing a suitable fuse.

Circuit symbols
Fuse: continuity and selectionIsolated, de-energized component. Recognizing an open circuit is different from choosing a suitable fuse. Fuse element → Resistance check → Selection dataDE-ENERGIZED · ISOLATED COMPONENTΩClosedA · V AC/DC · class · interrupting rating

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Continuous path · DE-ENERGIZED · ISOLATED COMPONENT. Continuity does not confirm class, interrupting rating or cause of failure.

Think before continuing

Are two fuses with the same amperage necessarily equivalent?

Show explanation

No. Other application and manufacturer requirements must match. Also investigate why the original opened.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Is a fuse compatible just because it fits the holder?

View the explained answer

No. Size and amperage do not replace checking all required characteristics.

LECCIÓN 03.9

Solenoid valves: electrical control and fluid circuit

The coil actuates a mechanism controlling fluid passage. NC and NO are defined relative to the de-energized coil. Identify the exact body and coil: voltage, AC/DC, frequency, refrigerant, pressure, temperature and allowed direction.

Evaluate coil resistance de-energized using its reference. In a pilot-operated valve, opening can also depend on pressure differential. Neither a click nor an Ω reading alone proves correct flow. Stepper-motor electronic expansion requires another method.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Solenoid valve: coil and fluid passage

Ideal functional model. Pilot-operated valves may require pressure differential; an energized coil does not guarantee flow.

Functional diagram
Solenoid valve: coil and fluid passageIdeal functional model. Pilot-operated valves may require pressure differential; an energized coil does not guarantee flow. Coil → Body and mechanism → Fluid circuitCoil · OFFMechanismNC → ClosedFluid

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Ideal closed position; not a tightness test.

Think before continuing

Does hearing a click prove that correct flow is passing?

Show explanation

No. Verify circuit conditions and response using the model procedure.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Does an energized coil guarantee correct opening of a pilot-operated valve?

View the explained answer

No. That model’s fluid, refrigeration and mechanical conditions must also be met.

LECCIÓN 03.10

Dampers with motors and gears

An actuator converts a command into motion through a motor, gears and shaft coupling. Distinguish supply, command signal and feedback where present. There are on/off, floating and proportional versions; they do not all use the same range.

The LF24-SR US example uses a 24 V AC/DC supply and control configured for 2–10 V DC. In the ideal model, 6 V is mid-travel, not half the airflow. Its spring returns to a safety position on power loss; the end stop depends on mounting. Motorized return requires energy and is a different architecture.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Damper: signal, gears and position

LF24-SR US reference: 24 V AC/DC supply, 2–10 V DC control and spring return. Displayed position is an ideal relationship, not an airflow measurement.

Functional diagram
Damper: signal, gears and positionLF24-SR US reference: 24 V AC/DC supply, 2–10 V DC control and spring return. Displayed position is an ideal relationship, not an airflow measurement. Command and supply → Motor and gears → Damper bladeSupply 24 V AC/DCONY = 6 V CC/DCMotor + gearsDamperIdeal travel: 50.0 %

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

6 V CC/DC → Ideal travel: 50.0 %. Percentage of travel, not airflow.

Think before continuing

Does 50% actuator travel mean 50% airflow?

Show explanation

No. Airflow depends on the damper, pressure and system. Verify actual position and performance separately.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

The controller requests opening, but motion is not confirmed. Which elements do you distinguish?

View the explained answer

Supply, signal, configuration, actuator, coupling, travel and damper motion; check them according to the manual without assuming which one is the cause.

Sources for further study

Reference readings: some resources are in English. Consult the current equipment manual before any work. Access to restricted documentation is not assumed.