AC DOCTOR COOL · 24 VISUAL LABS
Learn with interactive diagrams
Trace the path, identify each component and test an idea. Start with symbols and circuits, then explore refrigeration, measurements and complex systems.
1. Read the theory. 2. Select components. 3. Change one condition. 4. Explain the result before opening the answer.
How to read the drawings and their references
Circuit symbols and functional blocks are identified in each drawing. IEC 60617 addresses electrical symbols; ISO 14617-2:2025 addresses industrial symbols and refers electrical symbols to IEC. A standard does not automatically certify an educational drawing.
Electrical conventions: IEC 60617; shapes checked against Eaton, chapter 9. Refrigeration drawings are functional diagrams based on manufacturer documentation. These drawings are not claimed to be IEC/ISO certified.
References reviewed: October 20, 2026.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Read an electrical schematic
Recognize a junction, resistor, capacitor and contact before tracing a circuit.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
A filled dot joins conductors. A crossing without a dot is not a junction in these drawings.
Think before continuing
Does a crossing without a dot always connect two wires?
Show explanation
No. In this legend, only a dot indicates a junction. Check each document’s convention.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Series and parallel: see Ohm’s law
Ideal virtual resistive circuit at 24 V DC. Change the topology and R1; compare current, voltage and equivalent resistance.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
The ideal source maintains 24 V across its terminals. This is a mathematical example, not a recommended build.
Equivalent resistance: 36.00 Ω · Total current: 0.67 A. R1: 8.00 V / 0.67 A. R2: 16.00 V / 0.67 A. Ideal resistive model; does not represent an AC motor.
Think before continuing
With R1 = 12 Ω and R2 = 24 Ω, which connection draws more source current?
Show explanation
Parallel: Req = 8 Ω and I = 3 A. In series: Req = 36 Ω and I ≈ 0.67 A. These are ideal resistors, not an AC motor calculation.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
One quantity, one connection
Explore conceptual meter placement in an ideal circuit. Real equipment measurements require trained personnel and a suitable instrument.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
For resistance or continuity, this example completely disconnects the supply and isolates the component.
Voltmeter in parallel: 24 V DC
Think before continuing
Does a continuity beep prove that a component is exactly 0 Ω?
Show explanation
No. It indicates a condition relative to the instrument threshold. Read the value and consult its manual.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Control and power: a relay
Two separate circuits. The coil operates a contact through a mechanical link; there is no wire between those functions.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Demand closes the contact in the ideal control circuit. Real equipment also includes safeties and a specific sequence.
Coil at rest; NO contact open.
Think before continuing
Is the dashed line between coil and contact a conductor?
Show explanation
No: it represents mechanical actuation. The electrical circuits remain separate.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
AC → DC → variable AC
Blocks in a typical electronic conversion. This is not a circuit-board schematic or a terminal map.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Converts the AC input into a unidirectional output. A diode bridge is a common implementation; other architectures exist.
Think before continuing
Are mains Hz enough to know inverter compressor speed?
Show explanation
No. The output stage and controller regulate the motor. Consult the manufacturer’s variables and methods.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
The refrigerant path
Vapor-compression cycle in cooling mode. Pressure, phase and heat transfer are different concepts.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Receives low-pressure vapor and discharges it at high pressure; requires work.
Think before continuing
Does the entire low-pressure path contain only vapor?
Show explanation
No: there is a liquid/vapor mixture after expansion. Low pressure does not imply a single phase.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Cooling and heating: roles change
Compare exchanger roles. The reversing valve changes connections; the compressor does not pump backward.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
In cooling it absorbs heat from the space; in heating it delivers heat to the space.
Heat exchange changes; valve piping is not shown.
Think before continuing
Does switching to heating reverse compressor pumping direction?
Show explanation
No. Connections and exchanger roles change; suction and discharge retain their functions.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Return air, supply air and ventilation
Functional air path. Actual fan, filter and coil positions depend on the design.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Brings room air back for conditioning. Recirculation does not guarantee outdoor air intake.
Recirculation only in this example.
Think before continuing
If the fan runs, do we know that fresh air is entering?
Show explanation
No. Toggle the drawing’s outdoor inlet: recirculation can operate without outdoor ventilation.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Saturation, superheat and subcooling
R-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Identify refrigerant, unit and pressure location. This example uses psig, not absolute pressure.
R-454B · 110 psig · Dew 41.1 °F. SH = 55.1 − 41.1 = 14.0 °F (7.8 °C). Pipe temperature chosen for the exercise; not an adjustment target.
Think before continuing
For R-454B, do SH and SC use the same saturation column?
Show explanation
No. Dew point for superheat; bubble point for subcooling. Do not apply this chart to R-410A or R-32.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Vacuum: measure the isolated system
Example criterion: Lennox EL16KC1, page 23, no rise above 500 microns during 20 minutes of isolation. Always check the model procedure.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
The vacuum gauge must represent the system. Here it is on the system side of the isolation valve.
This hypothetical record meets the stated 500-micron / 20-min criterion. Exercise curves, connected by segments; not real measurements.
Think before continuing
Is reaching 400 microns with the pump running enough to pass this criterion?
Show explanation
No. The isolation period is also evaluated. These two records are exercises, not real equipment results or a universal proof of no leaks.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Chiller: circuits that do not mix
Follow energy from the building through the refrigerant to outdoors. Heat-transfer lines are not pipes connecting fluids.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Water exchanges heat with the load and evaporator without entering the refrigerant circuit.
Three separate circuits; they only exchange heat.
Think before continuing
Does chilled water mix with refrigerant in the evaporator?
Show explanation
No. They exchange energy through heat-exchanger surfaces while remaining separate.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
VRF: one network, several zones
Conceptual network: each line represents a circuit relationship, not the number of pipes. Communication is shown separately.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
The system regulates refrigerant to serve zones within approved combinations and limits.
Think before continuing
Does every VRF allow simultaneous cooling and heating?
Show explanation
No. It must be a heat-recovery variant with an approved configuration. Check the model.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
From measurement to response
Functional control loop. Select a stage and explain what evidence you would need before attributing a fault to it.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Converts a physical variable into a signal. Its reading needs context, location and a manufacturer reference.
Think before continuing
Does a sensor alarm prove it needs replacement?
Show explanation
No. Conditions, signal and connections are checked according to the manufacturer’s procedure.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Marine AC: water and refrigerant separated
Functional seawater path in an MCS system. It does not represent heights, mounting positions or an installation plan.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
The path begins at the intake and passes through the strainer. Installation and seacock requirements are checked in the manual.
Think before continuing
Does seawater enter the refrigerant piping?
Show explanation
No. Both fluids remain separated by the heat exchanger.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Dual capacitor: C, HERM and FAN
TEMCo RC0102: 35/5 µF, ±5%. Two sections share C. Select a section to measure µF in this isolated, discharged virtual model. Hz is frequency, not capacitance.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Internally joins both sections. It does not automatically mean neutral or the compressor C terminal.
C–HERM · 35 µF ±5% · Section interval: 33.25–36.75 µF. Hypothetical reading: 35.00 µF. Reading within nominal tolerance. Also consider accuracy and procedure; this does not certify the capacitor.
Think before continuing
Does a 35 + 5 µF label mean measuring 40 µF between C and HERM?
Show explanation
No: there are two sections. In this example, C–HERM corresponds to 35 µF and C–FAN to 5 µF. Evaluate them separately using the nameplate tolerance.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Contactor: poles and coil
Ideal two-pole NO contactor. The drawing changes position without energizing real equipment. L/T identify power terminals; A1/A2 identify the coil.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Check continuity without voltage and with the component isolated. An NO pole opens at rest and closes when operated in this example.
L1–T1: Open · L2–T2: Open. DE-ENERGIZED · ISOLATED COMPONENT
Think before continuing
Is a higher-amp contactor always a suitable replacement?
Show explanation
No. Check poles, load application, FLA/LRA, voltage, AC/DC coil and frequency, auxiliary contacts and equipment approval.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Single-phase compressor: C, R and S
Teaching equivalent of two single-phase windings, without a supply. It does not apply directly to three-phase or inverter compressors.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
This is the common point of the displayed windings. Confirm physical C/R/S locations with the manufacturer.
C–R = 1 Ω. Hypothetical winding values; not a compressor specification.
Think before continuing
If C–R = 1 Ω and C–S = 2 Ω in this example, what do you expect between R and S?
Show explanation
Approximately 3 Ω, accounting for lead and connection effects. This sum does not prove correct insulation or compressor mechanical health.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Temperature and resistance: NTC / PTC
Three typical CAREL points: NTC 10 kΩ / β3435 and PTC KTY81/121. These are not a universal table or acceptance limits.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
NTC resistance decreases as temperature rises. PTC resistance increases, within its operating range.
NTC 10 kΩ / β3435 · 25 °C → 10000 Ω. Typical CAREL reference value; check the installed sensor table and tolerance.
Think before continuing
Do all “10 kΩ” sensors have the same curve?
Show explanation
No. That rating needs a reference temperature; curve, tolerance and controller compatibility also matter.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
NO and NC: the reference state
NO = normally open; NC = normally closed, relative to a defined reference state. They do not mean “equipment running” or “equipment faulty”.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
In this example it is open when not actuated and closed when actuated.
NO: Open · NC: Closed.
Think before continuing
Does an NC contact always have continuity?
Show explanation
No. It describes its normal reference state; it may open when actuated.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Pressure switch and transducer: two signals
Choose contact-based permission or an analog signal. Physical pressure and electricity are different domains.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Protection responds to the manufacturer-defined condition. This example opens permission on high pressure; it sets no cutoff pressure.
Permission path closed in this example.
Think before continuing
Is an active transducer diagnosed like a switch?
Show explanation
No. Identify its supply, output, range and exact procedure. Do not bypass safeties to force equipment operation.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Transformer: 24 V AC and VA rating
TR40VA002US nominal example: 120 V AC primary, 24 V AC secondary, 40 VA. The exercise adds loads; it does not size protective devices.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Receives the specified voltage and frequency. Taps and colors depend on the model.
Hypothetical load: 24 VA / 24 V = 1.00 A. Nominal rating: 40 VA / 24 V ≈ 1.67 A. Within the nominal 40 VA; inrush and conditions still need checking. This calculation does not select the fuse.
Think before continuing
Is a 48 VA load within a 40 VA nominal rating?
Show explanation
No. It exceeds the example rating. Even below 40 VA, inrush, conditions and approved selection need checking.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Fuse: continuity and selection
Isolated, de-energized component. Recognizing an open circuit is different from choosing a suitable fuse.
Circuit symbolsOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
An open element interrupts the electrical path. An isolated test avoids mistaking parallel paths for fuse continuity.
Continuous path · DE-ENERGIZED · ISOLATED COMPONENT. Continuity does not confirm class, interrupting rating or cause of failure.
Think before continuing
Are two fuses with the same amperage necessarily equivalent?
Show explanation
No. Other application and manufacturer requirements must match. Also investigate why the original opened.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Solenoid valve: coil and fluid passage
Ideal functional model. Pilot-operated valves may require pressure differential; an energized coil does not guarantee flow.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
Identify AC/DC voltage, frequency and compatibility. Evaluate resistance without voltage using the manufacturer reference.
Ideal closed position; not a tightness test.
Think before continuing
Does hearing a click prove that correct flow is passing?
Show explanation
No. Verify circuit conditions and response using the model procedure.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.
THEORY → DIAGRAM → VIRTUAL PRACTICE
Damper: signal, gears and position
LF24-SR US reference: 24 V AC/DC supply, 2–10 V DC control and spring return. Displayed position is an ideal relationship, not an airflow measurement.
Functional diagramOn small screens, scroll the drawing horizontally. Every component is also available as a button.
Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.
Select a component or follow the sequence.
The command signal does not replace the supply. Other models use on/off, floating control or different ranges.
6 V CC/DC → Ideal travel: 50.0 %. Percentage of travel, not airflow.
Think before continuing
Does 50% actuator travel mean 50% airflow?
Show explanation
No. Airflow depends on the damper, pressure and system. Verify actual position and performance separately.
Sources and drawing scope
Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.