MÓDULO 11 · TÉCNICA

Installation and startup

From equipment selection to a documented, verifiable handover.

Intermediate3 lessonsEdition: Oct. 20, 2026

LESSON 11.1

Select and plan

Installation begins with load, application and selection, not with what physically fits. Review capacity, design conditions, air, electricity, drainage, noise, support, accessibility and the approved equipment combination.

Project documentation and local requirements determine permits and responsibilities. A fixed square-feet-per-ton rule does not replace a load calculation. The equipment must remain serviceable after installation.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Return air, supply air and ventilation

Functional air path. Actual fan, filter and coil positions depend on the design.

Functional diagram
Return air, supply air and ventilationFunctional air path. Actual fan, filter and coil positions depend on the design. Return → Filter → Coil → FanReturnFilterCoilFanRoomSupplyRecirculation only in this example.

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Recirculation only in this example.

Think before continuing

If the fan runs, do we know that fresh air is entering?

Show explanation

No. Toggle the drawing’s outdoor inlet: recirculation can operate without outdoor ventilation.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

What problem does correctly selected equipment create if there is no service space?

View the explained answer

It makes safe maintenance and repair difficult, may violate required clearances and increases future costs and risks.

LESSON 11.2

Workmanship quality

Supports, routing, insulation, joints, drainage and electrical protection must follow the design and manual. Lengths, diameters, elevation differences and torque values vary by model.

An apprentice first identifies the purpose of each check and records evidence under supervision. Brazing, pressurization, evacuation, charging and electrical work require specific training; this library does not replace their field procedures.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Vacuum: measure the isolated system

Example criterion: Lennox EL16KC1, page 23, no rise above 500 microns during 20 minutes of isolation. Always check the model procedure.

Functional diagram
Vacuum: measure the isolated systemExample criterion: Lennox EL16KC1, page 23, no rise above 500 microns during 20 minutes of isolation. Always check the model procedure. System → Vacuum gauge → Isolation → Vacuum pumpSystemVacuum gaugeIsolationPumpPump isolated50040004305450104601546020Time (min)Absolute pressure (microns)

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

This hypothetical record meets the stated 500-micron / 20-min criterion. Exercise curves, connected by segments; not real measurements.

Think before continuing

Is reaching 400 microns with the pump running enough to pass this criterion?

Show explanation

No. The isolation period is also evaluated. These two records are exercises, not real equipment results or a universal proof of no leaks.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Why keep a record of piping and changes during installation?

View the explained answer

It allows requirements to be verified, applicable calculations to be adjusted, and the next technician to have a reliable reference for what was actually installed.

LESSON 11.3

Verify and hand over

Startup verifies that the assembly operates according to manufacturer criteria: controls, air or water, drainage, the refrigerant circuit and protective devices. Environmental and load conditions accompany the results.

Handover includes the model, warranty documents, controls, maintenance information and the work record. Equipment that starts is distinguished from a system whose operation has been verified. Outstanding tests must be identified.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Saturation, superheat and subcooling

R-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences.

Functional diagram
Saturation, superheat and subcoolingR-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences. Pressure and P–T table → Pipe temperature → Temperature difference110 psigDew: 41.1 °FVapor55.1 °FSH = 14.0 °F

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

R-454B · 110 psig · Dew 41.1 °F. SH = 55.1 − 41.1 = 14.0 °F (7.8 °C). Pipe temperature chosen for the exercise; not an adjustment target.

Think before continuing

For R-454B, do SH and SC use the same saturation column?

Show explanation

No. Dew point for superheat; bubble point for subcooling. Do not apply this chart to R-410A or R-32.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

What should a handover include beyond “it is cooling”?

View the explained answer

What was verified, results and conditions, work performed, outstanding items, operating instructions and equipment documentation.

Sources for further study

Reference readings: some resources are in English. Consult the current equipment manual before any work. Access to restricted documentation is not assumed.