MODULE 06 · RESIDENTIAL

Split systems · Straight cool

Condensing units, air handlers and ducts in straight-cool systems.

Intermediate3 lessonsEdition: Oct. 20, 2026

LESSON 06.1

The indoor and outdoor combination

In a central split system, the outdoor unit and indoor coil work with an air handler or other air-moving equipment. Straight cool usually describes cooling without reversing the cycle for heating; the system may include a separate auxiliary heat source.

Selection considers refrigerant, the expansion device, capacity and airflow, as well as electrical and control compatibility. Replacing only one part requires verification of the approved combination and its performance.

THEORY → DIAGRAM → VIRTUAL PRACTICE

The refrigerant path

Vapor-compression cycle in cooling mode. Pressure, phase and heat transfer are different concepts.

Functional diagram
The refrigerant pathVapor-compression cycle in cooling mode. Pressure, phase and heat transfer are different concepts. Compressor → Condenser → Expansion → EvaporatorCompressorCondenserExpansionEvaporatorVapor · highLiquid · highMixture · lowVapor · lowReleases heatAbsorbs heat

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Think before continuing

Does the entire low-pressure path contain only vapor?

Show explanation

No: there is a liquid/vapor mixture after expansion. Low pressure does not imply a single phase.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Is matching tonnage enough when replacing a condensing unit?

View the explained answer

No. The indoor/outdoor combination, refrigerant, controls and installation conditions must be confirmed.

LESSON 06.2

Understand the operating sequence

A call for cooling starts a control sequence with delays and safety functions according to the design. The indoor fan, compressor and outdoor fan have different functions; one running does not prove the others are enabled.

The analysis follows the command from the thermostat to the equipment, using the exact diagram. Not all systems use conventional 24 V controls; some communicate digitally. A terminal letter is not permission to install a jumper.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Control and power: a relay

Two separate circuits. The coil operates a contact through a mechanical link; there is no wire between those functions.

Circuit symbols
Control and power: a relayTwo separate circuits. The coil operates a contact through a mechanical link; there is no wire between those functions. Control contact → Coil K1 → Contact K1 (NO) → Load MControlLoad+−K1+−MMechanical link24 V DC24 V DC

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

Coil at rest; NO contact open.

Think before continuing

Is the dashed line between coil and contact a conductor?

Show explanation

No: it represents mechanical actuation. The electrical circuits remain separate.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

There is indoor airflow but no cooling. What distinctions are useful in the diagnosis?

View the explained answer

Distinguish the demand, authorization from controls and safety devices, and the actual operation of each component before recommending a part.

LESSON 06.3

Check overall performance

A split system needs adequate heat exchange on both sides. Restricted indoor airflow, dirty coils, electrical problems or refrigerant-circuit faults can produce similar symptoms.

The temperature difference between return and supply must be interpreted with humidity, airflow, load and test conditions. A single temperature or pressure does not confirm correct charge or total capacity. Document conditions before and after the work.

THEORY → DIAGRAM → VIRTUAL PRACTICE

Saturation, superheat and subcooling

R-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences.

Functional diagram
Saturation, superheat and subcoolingR-454B: real Honeywell chart points and hypothetical pipe temperatures. These are exercises, not target charging pressures or temperature differences. Pressure and P–T table → Pipe temperature → Temperature difference110 psigDew: 41.1 °FVapor55.1 °FSH = 14.0 °F

On small screens, scroll the drawing horizontally. Every component is also available as a button.

Solid line: indicated path. Arrow: direction. Dashed line: signal or functional relationship. Labels identify every path; color is supplementary.

R-454B · 110 psig · Dew 41.1 °F. SH = 55.1 − 41.1 = 14.0 °F (7.8 °C). Pipe temperature chosen for the exercise; not an adjustment target.

Think before continuing

For R-454B, do SH and SC use the same saturation column?

Show explanation

No. Dew point for superheat; bubble point for subcooling. Do not apply this chart to R-410A or R-32.

Sources and drawing scope

Original teaching drawing, not to scale. Functional blocks do not represent terminals or installation connections. Use the model-specific diagram for real work.

Open all interactive diagrams →

Check your understanding

Does an apparently good temperature split prove that every room receives enough air?

View the explained answer

No. There may be a distribution or airflow problem. The evaluation must include the air system and measurement conditions.

Sources for further study

Reference readings: some resources are in English. Consult the current equipment manual before any work. Access to restricted documentation is not assumed.